PRODUCTS | INSTRUMENTATION CABLES

 

RE-2X(St)HSWAH-PiMF

Application

Instrumentation cables are preferred in the industrial applications of petrochemical plants, power plants, steel & aluminium factories, water treatment plants, pipelines and industrial buildings of the oil and gas industry and similar projects where measurement and control of data is crucial and the project environment can be demanding. Birikim Kablo follows national/international standards or customers specific requests when designing these cables.

Construction
Reference Standard EN 50288-7
Conductor IEC 60228, CLASS-2 Stranded electrolytic annealed copper wire
Insulation XLPE | EN 50290-2-29
Colour Code Pair : White-black cores  with numbers       
Triple : White-black-red cores  with numbers                                         
Drain wire Tinned solid copper wire
Individual screen Polyester tape, Aluminium foil 100% coverage

Lay up

Two cores twisted in pair and pairs stranded together
Screen Polyester tape, Aluminium foil 100% coverage
Drain wire Stranded Tinned Copper
Inner sheath HFFR | EN 50290-2-27
Armour Galvanized steel wire armour
Outer sheath HFFR | EN 50290-2-27
Outer sheath color RAL 5015 Blue / RAL 9005 Black
         
Specifications
Mutual Capacitance (800 MHz)  150(pF/m)
Capacitance Unbalance 500 pF/ 500 m
Insulation Resistance >5000MΩ.km
Conductor Resistance
Cross Section  (mm2) Conductor resistance Ω/km (max.) L/R Ratio(µH/Ω)
0,5 36 25
0,75 24,5 25
1 18,1 25
1,3 14,2 40
1,5 12,1 40
2,5 7,41 60
Operating Voltage 300/500 V
Test Voltage 2000 V
Temperature Range -30°C   –   +90°C (fixed)
Min. Bending Radius 12 x  cable diameter
Smoke Density IEC 61034-2, EN 61034-2
Corressive Gas Tests IEC 60754-1, EN 50267-2
Oil Resistance ICEA S-82-552
Flame tests IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-2-1 
IEC 60332-3-24 , EN 60332-3-24 
Alternative designs: Yw – Heat resistant PVC (105 °C)
TiMF and QiMF screen types
C – Copper or tinned copper braided
Yv/Hv – Reinforced outer sheath
RE-2G - Fire resistant (silicon based)
RE-m2X - Fire resistant (mica tape based)
Communication core can be added upon request