PRODUCTS | INSTRUMENTATION CABLES

 

RE-2X(St)HSWBH-PiMF

RE-2X(St)HSWBH-PiMF

Application

Instrumentation cables are preferred in the industrial applications of petrochemical plants, power plants, steel & aluminium factories, water treatment plants, pipelines and industrial buildings of the oil and gas industry and similar projects where measurement and control of data is crucial and the project environment can be demanding. Birikim Kablo follows national/international standards or customers specific requests when designing these cables.

Construction
Reference Standard EN 50288-7
Conductor IEC 60228, CLASS-2 Stranded electrolytic annealed copper wire
Insulation XLPE | EN 50290-2-29
Colour Code Pair : White-black cores  with numbers      
Triple : White-black-red cores  with numbers                                         
Drain wire Tinned solid copper wire
Individual screen Polyester tape, Aluminium foil 100% coverage

Lay up

Two cores twisted in pair and pairs stranded together
Screen Polyester tape, Aluminium foil 100% coverage
Drain wire Stranded Tinned Copper
Inner sheath HFFR | EN 50290-2-27
Armour Galvanized steel wire braiding
Outer sheath HFFR | EN 50290-2-27
Outer sheath color RAL 5015 Blue / RAL 9005 Black
         
Specifications
Mutual Capacitance (800 MHz)  150(pF/m)
Capacitance Unbalance 500 pF/ 500 m
Insulation Resistance >5000MΩ.km
Conductor Resistance
Cross Section  (mm2) Conductor resistance Ω/km (max.) L/R Ratio(µH/Ω)
0,5 36 25
0,75 24,5 25
1 18,1 25
1,3 14,2 40
1,5 12,1 40
2,5 7,41 60
Operating Voltage 300/500 V
Test Voltage 2000 V
Temperature Range -30°C   –   +90°C (fixed)
Min. Bending Radius 10 x  cable diameter
Smoke Density IEC 61034-2, EN 61034-2
Corressive Gas Tests IEC 60754-1, EN 50267-2
Oil Resistance ICEA S-82-552
Flame tests IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-2-1
IEC 60332-3-24 , EN 60332-3-24 
Alternative designs: Yw – Heat resistant PVC (105 °C)
TiMF and QiMF screen types
C – Copper or tinned copper braided
Yv/Hv – Reinforced outer sheath
RE-2G - Fire resistant (silicon based)
RE-m2X - Fire resistant (mica tape based)
Communication core can be added upon request
   
Product Code  Number of  Cores × Cross section (mm2) Cable Diameter (mm ±5%) Copper Weight  (kg/km) Cable Weight  (kg/km)
33112110504 2x2x0,50 12,2 35 227
33112110508 4x2x0,50 13,8 59 290
33112110516 8x2x0,50 16,8 107 445
33112110520 10x2x0,50 19,4 132 558
33112110524 12x2x0,50 20,6 156 630
33112110532 16x2x0,50 23 204 800
33112110540 20x2x0,50 24,1 254 960
33112110548 24x2x0,50 27,6 304 1100
         
33112110804 2x2x0,75 13 46 252
33112110808 4x2x0,75 14,8 80 350
33112110816 8x2x0,75 17,8 150 525
33112110820 10x2x0,75 21,2 182 640
33112110824 12x2x0,75 22,3 216 785
33112110832 16x2x0,75 24,9 284 910
33112110840 20x2x0,75 26,8 352 1040
33112110848 24x2x0,75 29,4 420 1260
         
33112111004 2x2x1,0 14 56 278
33112111008 4x2x1,0 16,1 100 405
33112111016 8x2x1,0 20,2 188 600
33112111020 10x2x1,0 22,7 232 765
33112111024 12x2x1,0 23,8 275 860
33112111032 16x2x1,0 27 363 1040
33112111040 20x2x1,0 29,2 450 1205
33112111048 24x2x1,0 31,3 536 1510
         
33112111304 2x2x1,3 14,9 70 330
33112111308 4x2x1,3 17,6 136 455
33112111316 8x2x1,3 22 262 740
33112111320 10x2x1,3 24,9 320 895
33112111324 12x2x1,3 26,6 378 1080
33112111332 16x2x1,3 29 498 1280
33112111340 20x2x1,3 32,9 620 1580
33112111348 24x2x1,3 35,6 742 1900
         
33112111504 2x2x1,5 15,8 80 349
33112111508 4x2x1,5 18,6 140 500
33112111516 8x2x1,5 23,3 266 820
33112111520 10x2x1,5 25,4 322 960
33112111524 12x2x1,5 27,3 390 1080
33112111532 16x2x1,5 30,9 516 1410
33112111540 20x2x1,5 33,8 638 1635
33112111548 24x2x1,5 37,3 764 2040