PRODUCTS | FIRE RESISTANT CABLES

LIH(St)CH FE180 PH120

LIH(St)CH FE180 PH120

Quality Certificates

You can click on the logos to see the Quality Certificates.

Application

These cables are used in industrial electronics, control engineering applications, electronic devices and automation systems, fire alarm and supression systems especially in public buildings such as hotels, schools, hospitals, shopping centers etc. They have low smoke density and they don’t emit poisonous and corrosive gases during a fire therefore they don’t harm human health. They can function under flame for 180 minutes according to tests done as per IEC 60331-21 and maintain 120 minutes circuit integrity according to tests done as per EN50200 which simulate the fire and hazardous conditions.

Construction
Conductor IEC 60228, EN 60228, VDE 0295 CLASS-5 Stranded electrolytic annealed copper wire
Insulation Cross-linked elastomer silicone insulation | BS EN 50363-1, HD 22.1 S4(EI2)
Colour Code DIN 47100                      
Lay up Cores stranded in layers
Separator Polyester tape
Flame Barrier Fiberglass tape
Screen Aluminium foil 100% coverage, Tinned copper wire braiding
Outher sheath HFFR | EN 50290-2-27, VDE0207(HM2)
Outher Sheath Colour RAL 2004 Orange
Specifications
Conductor Resistance
Cross section (mm2) Ω/km (max.)
0,75 26
1,0 19,5
1,5 13,3
2,5 7,98
Insulation Resistance >200MΩ.km
Operating Voltage 300/500 V
Test Voltage 1000 V
Temperature Range -30°C   –   +90°C (fixed)
Min. Bending Radius 7,5 x  cable diameter
Flame tests IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-2-1 
Smoke Density IEC 61034-2, EN 61034-2
Corressive Gas Tests IEC 60754-1, EN 50267-2
Circuit Integrity Tests                FE180 IEC 60331-21
Circuit Integrity Tests  PH120 EN 50200
         
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401400802 2x0,75 6,5 24 55
3401400803 3x0,75 6,9 32 65
3401400804 4x0,75 7,5 38 76
3401400805 5x0,75 8,4 48 95
3401400807 7x0,75 8,8 62 120
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401401002 2x1,00 6,9 30 60
3401401003 3x1,00 7,2 38 75
3401401004 4x1,00 8 47 95
3401401005 5x1,00 8,7 60 115
3401401007 7x1,00 9,6 80 143
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401401502 2x1,50 7,7 40 80
3401401503 3x1,50 8,2 53 105
3401401504 4x1,50 8,9 68 130
3401401505 5x1,50 10,5 84 144
3401401507 7x1,50 11,1 110 215