PRODUCTS | FIRE RESISTANT CABLES

LIHH FE180 PH120

LIHH FE180 PH120

Quality Certificates

You can click on the logos to see the Quality Certificates.

Application

These cables are used in industrial electronics, control engineering applications, electronic devices and automation systems, fire alarm and supression systems especially in public buildings such as hotels, schools, hospitals, shopping centers etc. They have low smoke density and they don’t emit poisonous and corrosive gases during a fire therefore they don’t harm human health. They can function under flame for 180 minutes according to tests done as per IEC 60331-21 and maintain 120 minutes circuit integrity according to tests done as per EN50200 which simulate the fire and hazardous conditions.

Construction
Conductor IEC 60228, EN 60228, VDE 0295 CLASS-5 Stranded electrolytic annealed copper wire
Insulation Cross-linked elastomer silicone insulation | BS EN 50363-1, HD 22.1 S4(EI2)
Colour Code DIN 47100                      
Lay up Cores stranded in layers
Separator Polyester tape
Flame Barrier Fiberglass tape
Outher sheath HFFR | EN 50290-2-27, VDE0207(HM2)
Outher Sheath Colour RAL 2004 Orange
Specifications
Conductor Resistance
Cross section (mm2) Ω/km (max.)
0,75 26
1,0 19,5
1,5 13,3
2,5 7,98
Insulation Resistance >200MΩ.km
Operating Voltage 300/500 V
Test Voltage 1000 V
Temperature Range -30°C   –   +90°C (fixed)
Min. Bending Radius 7,5 x  cable diameter
Flame tests IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-2-1 
Smoke Density IEC 61034-2, EN 61034-2
Corressive Gas Tests IEC 60754-1, EN 50267-2
Circuit Integrity Tests FE180 IEC 60331-21
Circuit Integrity Tests  PH120 EN 50200
         
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401100802 2x0,75 5,8 12,8 36
3401100803 3x0,75 6,4 19,2 46
3401100804 4x0,75 7,8 25 57
3401100805 5x0,75 8 32,5 70
3401100806 6x0,75 8,5 39 86
3401100808 8x0,75 9 52 107
3401100810 10x0,75 11,7 65 135
3401100820 20x0,75 14,8 129,5 252
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401101002 2x1,00 6 16,9 44
3401101003 3x1,00 6,3 25,5 58
3401101004 4x1,00 7,4 33,8 73
3401101005 5x1,00 8,1 42,5 88
3401101006 6x1,00 8,8 51 104
3401101008 8x1,00 10 68 135
3401101010 10x1,00 11,9 86 165
3401101020 20x1,00 15,4 174 315
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401101502 2x1,50 7,3 25,5 56
3401101503 3x1,50 7,8 38,5 77
3401101504 4x1,50 8,6 50,6 96
3401101505 5x1,50 10,2 63,8 125
3401101506 6x1,50 10,6 75,8 148
3401101508 8x1,50 11,8 101,2 180
3401101510 10x1,50 14 127 235
3401101520 20x1,50 17,9 257,4 440
Product Code Number of  Cores ×Cross Section (mm²) Cable Diameter (mm ±5%)  Copper Weight (kg/km) Cable Weight (kg/km)
3401102502 2x2,50 8,6 42 85
3401102503 3x2,50 9,1 62,4 113
3401102504 4x2,50 10,6 83,8 145
3401102505 5x2,50 11,8 104,5 180
3401102506 6x2,50 12,4 125 218
3401102508 8x2,50 13,8 168,5 282
3401102510 10x2,50 15,9 211 345
3401102520 20x2,50 20,6 425 668