LI2Y(St)CH-TP PiMF RS 232/422
Application | |||
They are used in data and information communication in electronic control systems. | |||
Construction | |||
Conductor | Stranded tinned electrolytic annealed copper wire | ||
Insulation | PE | EN 50290-2-23 | ||
Colour Code | Black/red – black/White – black/green – black/blue | ||
Lay up | Two cores twisted in pair | ||
Separator | Polyester tape | ||
Individual screen | Aluminium foil 100% coverage, Tinned copper drain wire | ||
Lay up | Two cores twisted in pair and pairs stranded together | ||
Separator | Polyester tape | ||
Foil Screen | Aluminium foil 100% coverage, Tinned copper drain wire | ||
Screen | Tinned copper wire braiding | ||
Outer sheath | HFFR | EN 50290-2-27, VDE0207(HM2) | ||
Outer Sheath Colour | RAL 7001 Grey | ||
Specifications | |||
Cross Section(mm2) Ω/km (max.) | |||
Loop resistance | 0,22mm² 186 | ||
0,34mm² 115 | |||
0,50mm² 78 | |||
Mutual Capacitance | 52 pF/m | ||
Impedance | 100±15 Ω | ||
Insulation Resistance | >2000MΩ.km | ||
Operating Voltage | 250 V | ||
Test Voltage | 1,2 kV | ||
Temperature Range | -30°C – +70°C / (fixed) | ||
Min. Bending Radius | 10 x cable diameter | ||
Smoke Density | IEC 61034-2, EN 61034-2 | ||
Corrosive Gas Tests | IEC 60754-1, EN 50267-2 | ||
Flame Tests | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-2-1 |