Application | ||||
These cables with halogen-free material are generally used indoors in order to protect human life and valuable goods in the case of fire. The usage areas are: electronic control devices, servo motors, valves, public announcement systems and automation applications where cable flexibility and signal quality is vital. Shielded and braided types provide better protection against electromagnetic interference. |
||||
Construction | ||||
Reference Standard | VDE 0812 | |||
Conductor | IEC 60228, EN 60228, VDE 0295 CLASS-5 Stranded electrolytic annealed copper wire | |||
Insulation | HFFR | EN 50290-2-26, VDE0207(HI2) | |||
Colour Code | DIN 47100 | |||
Lay up | Cores stranded in layers | |||
Separator | Polyester tape | |||
Screen | Tinned copper wire braiding | |||
Inner sheath | HFFR | EN 50290-2-27, VDE0207(HM2) | |||
Separator | Polyester tape | |||
Screen | Tinned copper wire braiding | |||
Outher sheath | HFFR | EN 50290-2-27, VDE0207(HM2) | |||
Outher Sheath Colour | RAL 7001 Grey | |||
Specifications | ||||
Conductor Resistance | ||||
Cross Section (mm2) | Ω/km (max.) | |||
0,14 | 148 | |||
0,22 | 96 | |||
0,25 | 79,9 | |||
0,34 | 53 | |||
0,5 | 38,9 | |||
0,75 | 26 | |||
1 | 19,5 | |||
1,5 | 13,3 | |||
2,5 | 7,98 | |||
Operating Voltage | ||||
Cross Section (mm2) | Voltage | |||
0,14 – 0,34 | 250 V | |||
0,50 – 2,50 | 300/500 V | |||
Test Voltage | ||||
Cross Section (mm2) | Voltage | |||
0,14 - 0,22 | 800 V | |||
0,22 – 1,00 | 1200 V | |||
1,50 – 2,50 | 2500 V | |||
Insulation Resistance | >200MΩ.km | |||
Temperature Range | -30°C – +70°C (fixed) | |||
Min. Bending Radius | 7,5 x cable diameter | |||
Flame tests | IEC 60332-1-2, EN 60332-1-2, VDE 0482-332-2-1 | |||
Smoke Density | IEC 61034-2, EN 61034-2 | |||
Corrosive Gas Tests | IEC 60754-1, EN 50267-2 | |||