Application | |||
These cables are used in data communication and analogue systems that work up to 155 Mbit/s. Also support to ISDN, 10 Base-T Ethernet, 100 Base-T Ethernet, 1000 Base-T Ethernet, TP-PMD/TP-DDI, ATM SYSTEMS. These cables with halogenfree flame retardant characteristic are used in public places. They have low smoke density and they don’t emit poisonous and corrosive gases during a fire therefore they don’t harm human health. |
|||
Construction | |||
Conductor | Bare copper wire AWG24 | ||
Insulation | PE | EN 50290-2-23, VDE0207 | ||
Colour Code | EIA/TIA568.B2 | ||
Lay up |
Two cores twisted in pair and pairs stranded together | ||
Outer sheath | 5,10 mm HFFR | EN 50290-2-27, VDE0207(HM2) | ||
Outer Sheath Colour | RAL 7032 Grey | ||
Specifications | |||
Impedance | 100±15 Ω | ||
Mutual Capacitance | 48 pF/m | ||
Temperature Range | -30°C – +70°C / (fixed) | ||
Min. Bending Radius | 7,5 x cable diameter | ||
Cable Weight | 34 (kg/km) | ||
Standard Packing | 305 m Carton Box | ||
305 m Plywood Spool | |||
500 m Plywood Spool | |||
Loop Resistance | 180 Ω/km(max.) | ||
Insulation Resistance | >2000MΩ.km | ||
Operating Voltage | 250 V | ||
Test Voltage | 1,2 kV | ||
Smoke Density | IEC 61034-2, EN 61034-2 | ||
Corrosive Gas Tests | IEC 60754-1, EN 50267-2 | ||
Electrical Properties | |||
Frequency | Attenuation | NEXT | Return Loss |
(MHz) | (dB/100m) Max. | (dB/100m) Min. | (dB/100m) Min. |
1 | 2 | 68,3 | 20 |
4 | 4 | 59,3 | 23 |
10 | 6,5 | 53,3 | 25 |
16 | 8 | 50,3 | 25 |
20 | 9 | 48 | 25 |
25 | 10,2 | 47,3 | 24 |
31,25 | 11 | 45,9 | 22 |
62,5 | 16,5 | 41,4 | 20 |
100 | 21 | 38,3 | 19 |
155 | 25,5 | 36,5 | 18 |